Engineering Analysis: 100W Metal Halide to LED Commercial Retrofit
Upgrading 100-watt Metal Halide fixtures (~122W system draw) to 35–50W LED cuts lighting load by 65%, delivering rapid payback on 12-to-24 hour commercial schedules.
1. Bare-Lamp Rating vs. Delivered LED Lumens (~6,000 lm)
A 100W Metal Halide lamp starts near 8,500 initial lumens, then depreciates to roughly 6,000 mean lumens (29% lower) over its operating life while still drawing full power. Sizing your LED replacement to ~6,000 delivered lumens (35–50W) matches or exceeds real-world working illuminance across a 50,000-hour L70 rating.
2. Eliminating Ballast Losses
HID lamps require a ballast (and on HPS/pulse-start MH, an ignitor) to strike and regulate the arc. On a 100W Metal Halide fixture, ballast losses add roughly 22W (22%), bringing true wall draw to ~122W. Switching to an integrated LED luminaire or Type B ballast-bypass lamp drops meter draw from ~122W to 35–50W.
3. Commercial Facility Savings (12 Hrs/Day at $0.13/kWh)
Operating 12 hours per day, 365 days per year (4,380 hours/yr):
- Per-Lamp / Per-Fixture Savings: Cuts 348 kWh/year, saving $45.27/year per unit.
- 25-Unit Facility Upgrade: Retrofitting 25 units reduces annual utility bills by $1131.68/year.
- Reduced Lift & Relamping Labor: High-bay, pole, and canopy fixtures often require scissor-lift or bucket-truck service calls. A 50,000+ hour LED rating eliminates multiple relamping and ballast-replacement cycles.
- Instant Restrike Safety: Metal halide lamps stay dark for 10–15 minutes after a momentary voltage dip; LEDs restore full workplace illumination instantly.
4. Primary Applications for 100W Metal Halide Retrofits
Commonly installed in small building wall packs, gas station and drive-through canopies, and auto dealership display lighting. Physical lamp specification: ED17 bulb with an E26 medium base (some fixtures use ED28 with an E39 mogul base).
A 100W MH lamp starts at about 8,500 lumens and averages about 6,000 over its life. A 35–50W LED delivers that working light level without the gradual dimming.
System draw with the ballast is about 122W; the LED replacement draws 35–50W in total.
Quick Reference: 100W Metal Halide Lamp vs. LED Replacement
| Spec | 100W Metal Halide lamp | LED replacement |
|---|---|---|
| ANSI ballast code | Pulse-start (read the M-code on the ballast label) | None (ballast removed / new fixture) |
| Bulb & base | ED17 bulb with an E26 medium base (some fixtures use ED28 with an E39 mogul base) | Type B corn bulb or integrated LED fixture |
| Light output | 8,500 initial / 6,000 mean bare-lamp lm | ~6,000 delivered lm |
| Power at the meter | ~122W including ballast | 35–50W |
| Color | ~3,700–4,200K, CRI ~65–70 (CMH: 80–90+) | 3000K–5000K, CRI 80–90+ |
| Rated life | 10,000–15,000 hours, varies by lamp | 50,000+ hours (L70), typical |
| Warm-up / restrike | 2–5 min warm-up / 10–15 min restrike | Instant |
What's Specific to the 100W Metal Halide Retrofit
Match 4000K to keep the familiar look
Standard metal halide renders at roughly 3,700–4,200K. A 4000K LED keeps the same crisp white look your customers are used to; a 5000K LED will look noticeably bluer next to any metal halide fixtures you have not converted yet.
Motion sensors finally make sense
Metal halide cannot be cycled with a motion sensor because it needs minutes to warm up and much longer to restrike. LED wall packs and canopy lights can run at low output overnight and jump to full brightness instantly when a car or person arrives.
Full-cutoff wall packs reduce glare
Many older 100W wall packs are forward-throw designs that shine into drivers' eyes and onto neighboring property. If you replace the whole fixture, a full-cutoff LED wall pack aims the light down where it is useful.
Sizing From Delivered Light (Worked Example)
HID catalog lumen ratings measure the bare lamp in 360 degrees, whereas IES LM-79 LED fixture ratings measure net light exiting the complete luminaire.
Example: targeting ~4,200 delivered lumens from an integrated LED luminaire operating at 140 lm/W requires roughly 30W — compared with ~122W on the existing 100W Metal Halide ballast circuit. For critical roadways, sports poles, or high-bay aisles, verify spacing with the manufacturer's IES photometric file.
5. Commercial Installation: Type B Ballast-Bypass Protocol
When retrofitting an existing housing with a Type B (ballast-bypass) LED lamp rather than replacing the whole fixture:
- Lock Out Power: Shut off and lock out the branch circuit breaker at the panel, then verify zero voltage at the fixture.
- Bypass the Ballast: Disconnect incoming line and neutral leads from the old ballast (and disconnect any ignitor and capacitor — leaving an HID ignitor in circuit sends multi-kilovolt pulses that will destroy an LED driver).
- Check Sockets & Wire Direct: Connect line voltage (typically 120–277V) to the lamp socket leads per the LED manufacturer's wiring diagram.
- Apply the Retrofit Label: Place the included modification sticker inside the luminaire housing warning future technicians that the ballast has been bypassed and legacy Metal Halide lamps must not be installed.